range of product |
EasyPact
|
|
---|---|---|
product or component type |
Circuit breaker
|
|
device short name |
Easypact EZC100H
|
|
circuit breaker name |
Easypact EZC100H
|
|
device application |
Distribution
|
|
poles description |
4P
|
|
protected poles description |
3t
|
|
network type |
AC
DC |
|
network frequency |
50/60 Hz
|
|
[In] rated current |
100?A at 40??C
|
|
[Ui] rated insulation voltage |
690?V AC 50/60 Hz conforming to IEC 60947-2
|
|
[Uimp] rated impulse withstand voltage |
6?kV conforming to IEC 60947-2
|
|
[Ue] rated operational voltage |
550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2 |
|
breaking capacity code |
H
|
|
breaking capacity |
10?kA Icu at 125 V DC 1P conforming to IEC 60947-2
10?kA Icu at 250 V DC 2P conforming to IEC 60947-2 10?kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 100?kA Icu at 110?130 V AC 50/60 Hz conforming to IEC 60947-2 20?kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50?kA Icu at 220?240 V AC 50/60 Hz conforming to IEC 60947-2 30?kA Icu at 380?400 V AC 50/60 Hz conforming to IEC 60947-2 30?kA Icu at 415 V AC 50/60 Hz conforming to IEC 60947-2 |
|
[Ics] rated service breaking capacity |
5?kA at 125 V DC conforming to IEC 60947-2
5?kA at 250 V DC conforming to IEC 60947-2 5?kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 2.5?kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 15?kA at 380?400 V AC 50/60 Hz conforming to IEC 60947-2 25?kA at 220?240 V AC 50/60 Hz conforming to IEC 60947-2 50?kA at 110?130 V AC 50/60 Hz conforming to IEC 60947-2 7.5?kA at 415 V AC 50/60 Hz conforming to IEC 60947-2 |
|
suitability for isolation |
Yes conforming to IEC 60947-2
|
|
utilisation category |
Category A
|
|
trip unit name |
TM-D
|
|
trip unit technology |
Thermal-magnetic
|
|
trip unit rating |
63?A at 50??C
|
|
protection type |
Overload protection
Short-circuit protection |
|
pollution degree |
3 conforming to IEC 60947
|
control type |
Toggle
|
|
---|---|---|
mounting mode |
Fixed
|
|
mounting support |
Backplate
|
|
upside connection |
Front
|
|
downside connection |
Front
|
|
mechanical durability |
8500?cycles
|
|
electrical durability |
Category A: 1500?cycles 415 V AC 50/60 Hz conforming to IEC 60947-2
|
|
connection pitch |
25?mm
|
|
local signalling |
Positive contact indication
|
|
neutral protection setting |
Without protection
|
|
earth-leakage protection |
Without
|
|
height |
130?mm
|
|
width |
100?mm
|
|
depth |
60?mm
|
range of product |
EasyPact
|
|
---|---|---|
product or component type |
Circuit breaker
|
|
device short name |
Easypact EZC250N
|
|
circuit breaker name |
Easypact EZC250N
|
|
device application |
Distribution
|
|
poles description |
3P
|
|
protected poles description |
3t
|
|
network type |
DC
AC |
|
network frequency |
50/60 Hz
|
|
[In] rated current |
250?A at 40??C
|
|
[Ui] rated insulation voltage |
690?V AC 50/60 Hz conforming to IEC 60947-2
|
|
[Uimp] rated impulse withstand voltage |
6?kV conforming to IEC 60947-2
|
|
[Ue] rated operational voltage |
550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2 |
|
breaking capacity code |
N
|
|
breaking capacity |
20?kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
50?kA Icu at 110?130 V AC 50/60 Hz conforming to IEC 60947-2 50?kA Icu at 220?240 V AC 50/60 Hz conforming to IEC 60947-2 20?kA Icu at 125 V DC 1P conforming to IEC 60947-2 20?kA Icu at 250 V DC 2P conforming to IEC 60947-2 25?kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 25?kA Icu at 400?415 V AC 50/60 Hz conforming to IEC 60947-2 8?kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 |
|
[Ics] rated service breaking capacity |
10?kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
25?kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2 10?kA at 125 V DC conforming to IEC 60947-2 10?kA at 250 V DC conforming to IEC 60947-2 25?kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2 4?kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 12.5?kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 12.5?kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 |
|
suitability for isolation |
Yes conforming to IEC 60947-2
|
|
utilisation category |
Category A
|
|
trip unit name |
TM-D
|
|
trip unit technology |
Thermal-magnetic
|
|
trip unit rating |
200?A at 50??C
|
|
protection type |
Overload protection
Short-circuit protection |
|
pollution degree |
3 conforming to IEC 60664-1
3 conforming to IEC 947-1 |
control type |
Toggle
|
|
---|---|---|
mounting mode |
Fixed
|
|
mounting support |
Backplate
|
|
upside connection |
Front
|
|
downside connection |
Front
|
|
mechanical durability |
10000?cycles
|
|
electrical durability |
Category A: 5000?cycles 415 V AC 50/60 Hz conforming to IEC 60947-2
|
|
connection pitch |
35?mm
|
|
local signalling |
Positive contact indication
|
|
neutral protection setting |
Without protection
|
|
earth-leakage protection |
Without
|
|
height |
165?mm
|
|
width |
105?mm
|
|
depth |
60?mm
|
A complete range of moulded case circuit-breakers up to 3200 A.
All the circuit-breakers, both three-pole and four-pole, are available in the fixed version; sizes T4 and T5 in the plug-in version and T4, T5, T6, and T7 also in the withdrawable one.
* High breaking capacity in compact dimensions
High values of short circuit breaking capacity are guaranteed at different voltage levels, without compromising overall dimensions.
* Flexibility of use
Thermomagnetic and electronic trip units are available for use in AC/DC or in AC only. It is possible to interchange trip units keeping the
same breaking part, so that installation can be upgraded with fewer costs.
* Advanced protection
A complete range of electronic trip units is suitable for different level of protection, even enhancing selectivity values with Early Fault
Detection and Prevention algorithm.
A26 contactors are mainly used for controlling 3-phase motors and generally for controlling power circuits up to 690 V AC or 220 V DC. The contactors can also be used for many other applications such as isolation, capacitor switching, lighting.
]]>range |
Easy9
|
|
---|---|---|
device application |
Distribution
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
Easy9 MCB
|
|
Poles |
2P
|
|
number of protected poles |
2
|
|
[In] rated current |
25?A
|
|
network type |
AC
|
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
10000?A Icn at 220 V AC 50/60 Hz conforming to IEC 60898-1
6000?A Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1 |
|
suitability for isolation |
Yes conforming to IEC 60898-1
|
network frequency |
50/60 Hz
|
|
---|---|---|
[Ue] rated operational voltage |
220 V AC 50/60 Hz
400 V AC 50/60 Hz |
|
magnetic tripping limit |
5?10 x In
|
|
[Ics] rated service breaking capacity |
6?kA 100?% x Icn at 230 V AC 50/60 Hz conforming to IEC 60898-1
|
|
[Ui] rated insulation voltage |
500?V AC 50/60 Hz conforming to IEC 60898-1
|
|
[Uimp] rated impulse withstand voltage |
4?kV conforming to IEC 60898-1
|
|
contact position indicator |
Yes
|
|
control type |
Toggle
|
|
local signalling |
Without
|
|
mounting mode |
Clip-on
|
|
mounting support |
DIN rail
|
|
9 mm pitches |
4
|
|
height |
81?mm
|
|
width |
36?mm
|
|
depth |
66.5?mm
|
|
colour |
Grey (RAL 7035)
|
|
mechanical durability |
10000?cycles
|
|
electrical durability |
4000?cycles
|
|
connections ? terminals |
Tunnel type terminal (top or bottom) 1?25?mm? rigid
Tunnel type terminal (top or bottom) 1?16?mm? flexible |
|
tightening torque |
2?N.m top or bottom
|
|
earth-leakage protection |
Without
|
standards |
IEC 60898-1
|
|
---|---|---|
product certifications |
CE
|
|
IP degree of protection |
IP20 conforming to IEC 60529
|
|
pollution degree |
2
|
|
tropicalisation |
2
|
|
relative humidity |
95?% at -5?60??C
|
|
ambient air temperature for operation |
-5?60??C
|
|
ambient air temperature for storage |
-40?85??C
|
?
]]>range of product |
C120
|
|
---|---|---|
range |
Acti 9
|
|
product name |
C120
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
C120H
|
|
device application |
Distribution
|
|
poles description |
3P
|
|
number of protected poles |
3
|
|
[In] rated current |
100?A
|
|
network type |
AC
|
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
15?kA Icu at <= 375 V DC conforming to EN/IEC 60947-2
15?kA Icu at 230?400 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
network frequency |
50/60 Hz
|
|
---|---|---|
[Ue] rated operational voltage |
<= 375 V DC
230?400 V AC 50/60 Hz |
|
magnetic tripping limit |
8 x In +/- 20 %
|
|
[Ics] rated service breaking capacity |
15?kA 100?% conforming to EN/IEC 60947-2 ? <= 375 V DC
7.5?kA 50?% conforming to EN/IEC 60947-2 ? 230?400 V AC 50/60 Hz |
|
limitation class |
3 conforming to EN/IEC 60947-2
|
|
[Ui] rated insulation voltage |
500?V AC 50/60 Hz conforming to EN/IEC 60947-2
|
|
[Uimp] rated impulse withstand voltage |
6?kV conforming to EN/IEC 60947-2
|
|
control type |
Toggle
|
|
local signalling |
ON/OFF indication
|
|
mounting mode |
Clip-on
|
|
mounting support |
35 mm symmetrical DIN rail
|
|
9 mm pitches |
9
|
|
height |
81?mm
|
|
width |
81?mm
|
|
depth |
73?mm
|
|
net weight |
0.615?kg
|
|
colour |
White
|
|
mechanical durability |
20000?cycles
|
|
electrical durability |
5000?cycles
|
|
connections ? terminals |
Tunnel type terminals1?50?mm? rigid
Tunnel type terminals1.5?35?mm? flexible |
|
wire stripping length |
15?mm
|
|
tightening torque |
3.5?N.m
|
|
earth-leakage protection |
Separate block
|
standards |
EN/IEC 60947-2
|
|
---|---|---|
IP degree of protection |
IP20 conforming to IEC 60529
|
|
pollution degree |
3 conforming to IEC 60947-2
|
|
overvoltage category |
III
|
|
tropicalisation |
2 conforming to IEC 60068-1
|
|
relative humidity |
95?% at 55??C
|
|
ambient air temperature for operation |
-30?70??C
|
|
ambient air temperature for storage |
-40?80??C
|